Refrigerated dryers work by cooling the air to low temperatures and condensing much of the water vapor. It is not possible to achieve dew points below freezing with a refrigerated dryer. Optimally designed refrigerated dryers can produce air with dew points to approximately 36°F (2°C). Since some water vapor is left in the air, these dryers should not be used in water sensitive applications.
All Industrial Gold Line of air dryers are simple to operate and install like our compressors. They use standard size inlet and outlet fittings with standard pipe thread.
Desiccant dryers pass the compressed air over a bed of desiccant material which absorbs water vapor molecules. Desiccant dryers can deliver air at consistently low dew points, typically -40°F/°C or less. Desiccant dryers are a good choice when the compressed air is subject to freezing conditions.
Model | Length Inches | Width Inches | Height Inches | CFM @ 100F Inlet | CFM @ 120 Deg Inlet | Max Inlet Temp | Voltage | Weight | Electronic Auto Drain | Refrigerant | Inlet/Outlet Size | Dew Point |
---|---|---|---|---|---|---|---|---|---|---|---|---|
RD10 | 13 | 13 | 15 | 10 | 8.8 | 120F | 115 | 64 | (Float) | R134a | 3/4 | 38F |
RD15 | 13 | 13 | 15 | 15 | 13.2 | 120F | 115 | 69 | Yes | R134a | 3/4 | 38F |
RD25 | 15 | 15 | 22 | 25 | 22 | 120F | 115 | 88 | Yes | R134a | 3/4 | 38F |
RD35 | 15 | 15 | 22 | 35 | 30.8 | 120F | 115 | 92 | Yes | R134a | 3/4 | 38F |
RD50 | 20 | 20 | 22 | 50 | 44 | 120F | 115 | 101 | Yes | R134a | 3/4 | 38F |
RD75 | 19 | 21 | 20 | 75 | 66 | 120F | 115 | 110 | Yes | R134a | 3/4 | 38F |
RD100 | 13 | 30 | 21 | 100 | 88 | 120F | 115 | 123 | Yes | R134a | 1 | 38F |
RD125 | 13 | 30 | 21 | 125 | 110 | 120F | 115 | 133 | Yes | R134a | 1 | 38F |
RD150 | 13 | 30 | 21 | 150 | 132 | 120F | 115 | 153 | Yes | R134a | 1 | 38F |
RD200 | 17 | 36 | 30 | 200 | 176 | 120F | 480/3 | 183 | Yes | R134a | 1 1/2 | 38F |
RD250 | 17 | 36 | 30 | 250 | 220 | 120F | 480/3 | 211 | Yes | R134a | 1 1/2 | 38F |
RD300 | 20 | 38 | 30 | 300 | 264 | 120F | 480/3 | 218 | Yes | R134a | 1 1/2 | 38F |
RD400 | 21 | 38 | 30 | 400 | 352 | 120F | 480/3 | 232 | Yes | R134a | 2 | 38F |
RD500 | 25 | 41 | 32 | 500 | 440 | 120F | 480/3 | 262 | Yes | R134a | 2 | 38F |
RD600 | 36 | 27 | 55 | 600 | 528 | 120F | 480/3 | 295 | Yes | R134a | 3 | 38F |
RD750 | 36 | 27 | 55 | 750 | 660 | 120F | 480/3 | 306 | Yes | R134a | 3 | 38F |
RD1000 | 36 | 27 | 55 | 1000 | 880 | 120F | 480/3 | 306 | Yes | R134a | 3 | 38F |
Model | Length Inches | Width Inches | Height Inches | cfm @ 100 Deg Inlet | cfm Req.for Max Operation | Max Inlet Temp | Voltage | Weight | Purge | Inlet/Outlet | Dew Point 10 Min. Cycle | Dew Point 4 Min. Cycle | Energy Efficent Model |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
HCT-40 | 32 | 32 | 46 | 40 | 46 | 120F | 115 | 365 | 6CFM | 1 | -40 | -100 | No |
HCS-40 | 32 | 32 | 46 | 40 | 46 | 120F | 115 | 365 | 6CFM | 1 | -40 | -100 | Yes |
HCT-60 | 32 | 32 | 61 | 60 | 69 | 120F | 115 | 445 | 9CFM | 1 | -40 | -100 | No |
HCS-60 | 32 | 32 | 61 | 60 | 69 | 120F | 115 | 445 | 9CFM | 1 | -40 | -100 | Yes |
HCT-90 | 32 | 32 | 78 | 90 | 103 | 120F | 115 | 575 | 13CFM | 1 | -40 | -100 | No |
HCS-90 | 32 | 32 | 78 | 90 | 103 | 120F | 115 | 575 | 13CFM | 1 | -40 | -100 | Yes |
HCT-115 | 38 | 44 | 54 | 115 | 132 | 120F | 115 | 685 | 17CFM | 1 | -40 | -100 | No |
HCS-115 | 38 | 44 | 54 | 115 | 132 | 120F | 115 | 685 | 17CFM | 1 | -40 | -100 | Yes |
HCT-165 | 38 | 44 | 54 | 165 | 189 | 120F | 115 | 685 | 24CFM | 1 | -40 | -100 | No |
HCS-165 | 38 | 44 | 54 | 165 | 189 | 120F | 115 | 685 | 24CFM | 1 | -40 | -100 | Yes |
HCT-260 | 38v | 48 | 72 | 260 | 298 | 120F | 115 | 1010 | 38CFM | 2 | -40 | -100 | No |
HCS-260 | 38 | 48 | 72 | 260 | 298 | 120F | 115 | 1010 | 38CFM | 2 | -40 | -100 | Yes |
HCT-370 | 38 | 55 | 63 | 370 | 424 | 120F | 115 | 1215 | 54CFM | 2 | -40 | -100 | No |
HCS-370 | 38 | 55 | 63 | 370 | 424 | 120F | 115 | 1215 | 54CFM | 2 | -40 | -100 | Yes |
HCT-450 | 38 | 55 | 71 | 450 | 515 | 120F | 115 | 1350 | 65CFM | 2 | -40 | -100 | No |
HCS-450 | 38 | 55 | 71 | 450 | 515 | 120F | 115 | 1350 | 65CFM | 2 | -40 | -100 | Yes |
HCT-590 | 48 | 52 | 101 | 590 | 675 | 120F | 115 | 1473 | 85CFM | 2 | -40 | -100 | No |
HCS-590 | 48 | 52 | 101 | 590 | 675 | 120F | 115 | 1473 | 85CFM | 2 | -40 | -100 | Yes |
HCT-750 | 48 | 54 | 104 | 750 | 858 | 120F | 115 | 2134 | 108CFM | 2 | -40 | -100 | No |
HCS-750 | 48 | 54 | 104 | 750 | 858 | 120F | 115 | 2134 | 108CFM | 2 | -40 | -100 | Yes |
HCT-930 | 56 | 59 | 109 | 930 | 1064 | 120F | 115 | 2414 | 134CFM | 2 | -40 | -100 | No |
HCS-930 | 56 | 59 | 109 | 930 | 1064 | 120F | 115 | 2414 | 134CFM | 2 | -40 | -100 | Yes |
HCT-1130 | 56 | 63 | 112 | 1130 | 1293 | 120F | 115 | 2875 | 163CFM | 3 | -40 | -100 | No |
HCS-1130 | 56 | 63 | 112 | 1130 | 1293 | 120F | 115 | 2875 | 163CFM | 3 | -40 | -100 | Yes |
Model | Length Inches | Width Inches | Height Inches | cfm @ 100 Deg. Inlet | cfm Req. for Max. Operation | Max Inlet Temp | Voltage | Weight | Purge | Inlet/Outlet | Dew Point 10 Min. Cycle | Dew Point 4 Min. Cycle |
---|---|---|---|---|---|---|---|---|---|---|---|---|
WM10 | 22.9 | 7 | 30.5 | 10 | 11 | 120F | 115 | 37 | 1 cfm | 1/2 | -40 | -100 |
WM15 | 22.9 | 7 | 30.5 | 15 | 17 | 120F | 115 | 54 | 2 cfm | 1/2 | -40 | -100 |
WM25 | 22.9 | 7 | 30.5 | 25 | 30 | 120F | 115 | 89 | 5 cfm | 1/2 | -40 | -100 |